Product information
The ODOT C-KIT-MTCP-32IO is a compact C-Series remote I/O introduction kit for Modbus TCP machines, SCADA systems and control panels. It combines a Modbus TCP network coupler with 16 digital inputs and 16 digital outputs, providing a practical 32-point starter configuration for decentralized sensor and actuator signals. Dual Ethernet ports support flexible line topology, while push-in wiring, channel-level LED indication and the slim DIN-rail design simplify installation and diagnostics. The modular platform can later be expanded with additional C-Series digital, analog, temperature, encoder and communication modules.
Specifications
- Quantity per product
- 1
- Short Description
Modbus TCP Coupler starter kit with 16 digital inputs, 16 digital outputs, dual Ethernet ports and modular expansion.
- Specifications
- Product type: Modbus TCP remote I/O introduction kit
- Included I/O: 16 digital inputs and 16 digital outputs
- Supported protocol: Modbus TCP Server
- Supported function codes: 01, 02, 03, 04, 05, 06, 15, 16 and 23
- Ethernet ports: 2 x RJ45, 10/100 Mbps
- Simultaneous connections: up to 5 Modbus TCP clients
- Maximum I/O expansion: 32 C-Series I/O modules
- Process data: maximum combined input and output size of 8192 bytes
- Backplane: 12 Mbit/s CAN bus
- Station refresh cycle: 2 ms with up to 32 modules
- Supply voltage: 24 VDC, 19.2 to 28.8 VDC
- Coupler power consumption: 50 mA at 24 VDC
- Digital input channels: 16, 24 VDC, PNP/high-level active
- Digital output channels: 16, 24 VDC, PNP/high-level active
- Isolation: system power isolated from field power
- Diagnostics: LED status indication on network adapter and individual I/O channels
- Operating temperature range: -35°C to +70°C horizontal; -35°C to +60°C vertical
- Storage temperature range: -40°C to +85°C
- Coupler dimensions: 115 x 51.5 x 75 mm
- Mounting method: 35 mm DIN rail
- Protection rating: IP20